Ensure that temperature controls have been installed as follows:
Automatic controls are preferred and should be installed where personnel are not available 24/7 on site to respond to and correct anomalies and situations.
Otherwise it is permissible for alarms to be used when temperatures fluctuate, requiring manual employee intervention. Note that use of alarms with manual intervention should also be supported by specific assessment within the organizational holistic risk assessment.
Check to see if temperature controls have been installed. Automatic controls are preferred and should be installed where personnel are not available 24/7 on site to respond to and correct anomalies and situations. Otherwise it is permissible for alarms to be used when temperatures fluctuate, requiring manual employee intervention.
NOTES:
1. In general such an area will be in raised floor space. The requirement should not be applied to administrative/office space. This requirement should also not be applied to a tactical environment, unless it is a fixed computer facility supporting missions in a Theater of Operations. The standards to be applied for applicability in a tactical environment are: 1) The facility containing the computer room has been in operation over 1-year. 2) The facility is "fixed facility" - a hard building made from normal construction materials - wood, steel, brick, stone, mortar, etc.
2. Use of alarms with manual intervention should be supported by specific assessment within the organizational holistic risk assessment.
V-30989
False
EC-05.03.01
Check to see if temperature controls have been installed. Automatic controls are preferred and should be installed where personnel are not available 24/7 on site to respond to and correct anomalies and situations. Otherwise it is permissible for alarms to be used when temperatures fluctuate, requiring manual employee intervention.
NOTES:
1. In general such an area will be in raised floor space. The requirement should not be applied to administrative/office space. This requirement should also not be applied to a tactical environment, unless it is a fixed computer facility supporting missions in a Theater of Operations. The standards to be applied for applicability in a tactical environment are: 1) The facility containing the computer room has been in operation over 1-year. 2) The facility is "fixed facility" - a hard building made from normal construction materials - wood, steel, brick, stone, mortar, etc.
2. Use of alarms with manual intervention should be supported by specific assessment within the organizational holistic risk assessment.