Environmental IA Controls - Fire Detection and Suppression

DISA Rule

SV-41037r3_rule

Vulnerability Number

V-30992

Group Title

Environmental IA Controls - Fire Detection and Suppression

Rule Version

EC-08.03.01

Severity

CAT III

CCI(s)

Weight

10

Fix Recommendation

An adequate fire detection and suppression system must be installed and must be periodically tested. The following considerations must be incorporated into the system:

1. A fully automatic fire detection and suppression system must be installed for information system areas that automatically activates when it detects heat, smoke, or particles.

2. A servicing fire department must receive an automatic notification of any activation of the smoke detection or fire suppression system.

3. Periodic testing of the fire detection and suppression system must be conducted.

4. The fire detection and suppression system(s) must be supported by an independent or alternate (backup) energy source.

Check Contents

1. Check to ensure a fully automatic fire detection and suppression system is installed for information system areas that automatically activates when it detects heat, smoke, or particles.

2. Check that a servicing fire department receives an automatic notification of any activation of the smoke detection or fire suppression system.

3. Check for periodic fire detection and suppression test logs.

4. Check the fire detection and suppression system(s) are supported by an independent or alternate (backup) energy source.

NOTES: This check applies primarily to facilities containing concentrations of information system resources including, for example, data centers, server rooms, and mainframe computer rooms. Fire suppression and detection devices/systems include, for example, sprinkler systems, handheld fire extinguishers, fixed fire hoses, and smoke detectors.

Vulnerability Number

V-30992

Documentable

False

Rule Version

EC-08.03.01

Severity Override Guidance

1. Check to ensure a fully automatic fire detection and suppression system is installed for information system areas that automatically activates when it detects heat, smoke, or particles.

2. Check that a servicing fire department receives an automatic notification of any activation of the smoke detection or fire suppression system.

3. Check for periodic fire detection and suppression test logs.

4. Check the fire detection and suppression system(s) are supported by an independent or alternate (backup) energy source.

NOTES: This check applies primarily to facilities containing concentrations of information system resources including, for example, data centers, server rooms, and mainframe computer rooms. Fire suppression and detection devices/systems include, for example, sprinkler systems, handheld fire extinguishers, fixed fire hoses, and smoke detectors.