STIGQter STIGQter: STIG Summary: Traditional Security Checklist Version: 1 Release: 3 Benchmark Date: 15 Jun 2020:

Vault/Secure Room Storage Standards - Intrusion Detection System (IDS) / Automated Entry Control System (AECS) Primary and Emergency Power Supply

DISA Rule

SV-41561r3_rule

Vulnerability Number

V-31290

Group Title

Vault/Secure Room Standards - IDS/AECS Power Supply

Rule Version

IS-02.02.05

Severity

CAT II

CCI(s)

Weight

10

Fix Recommendation

Fixes - Primary Power:

Fix #1. Ensure primary power for all Intrusion Detection System (IDS) equipment and Automated Entry Control system (AECS) equipment is either commercial AC or DC power.

Fix #2. Ensure that in the event of commercial power failure at either the secure room/area or monitor station, the equipment changes power sources without causing an intrusion alarm indication. An Uninterrupted Power Supply (UPS) will be required for this to occur.

Fixes - Emergency (Backup) Power:

Fix #1. Ensure that emergency power consists of a protected independent backup power source that provides a minimum of 8-hours operating battery and/or generator power. When batteries are used for emergency power, they shall be maintained at full charge by automatic charging circuits. The manufacturer's periodic maintenance schedule shall be followed and results documented.

Fix #2. Power Source and Failure Indication: Ensure that an illuminated indication exists at the Power Control Unit (PCU) of the power source in use (AC or DC).

Fix #3. Ensure equipment at the IDS/AECS monitor station indicates a failure in power source, a change in power source, and the location of the failure or change.

Check Contents

Primary Power Checks:

Check #1. Check to ensure primary power for all Intrusion Detection System (IDS) equipment and Automated Entry Control system (AECS) equipment is either commercial AC or DC power.

Check #2. Check to ensure that in the event of commercial power failure at either the secure room/area or monitor station, the equipment changes power sources without causing an intrusion alarm indication. An Uninterrupted Power Supply (UPS) will be required for this to occur.

Emergency (Backup) Power Checks:

Check #1. Check to ensure that emergency power consists of a protected independent backup power source that provides a minimum of 8-hours operating battery and/or generator power. When batteries are used for emergency power, they shall be maintained at full charge by automatic charging circuits. The manufacturer's periodic maintenance schedule shall be followed and results documented.

Check #2. Power Source and Failure Indication: Check to ensure that an illuminated indication exists at the Power Control Unit (PCU) of the power source in use (AC or DC).

Check #3. Check to ensure equipment at the IDS/AECS monitor station indicates a failure in power source, a change in power source, and the location of the failure or change.

TACTICAL ENVIRONMENT: This check is applicable where Vaults/Secure Rooms are used to protect classified materials or systems in a tactical environment. The only exception will be for urgent (short term) tactical operations or other contingency situations where fixed facilities and equipment are not yet present or incapable of being used.

Vulnerability Number

V-31290

Documentable

False

Rule Version

IS-02.02.05

Severity Override Guidance

Primary Power Checks:

Check #1. Check to ensure primary power for all Intrusion Detection System (IDS) equipment and Automated Entry Control system (AECS) equipment is either commercial AC or DC power.

Check #2. Check to ensure that in the event of commercial power failure at either the secure room/area or monitor station, the equipment changes power sources without causing an intrusion alarm indication. An Uninterrupted Power Supply (UPS) will be required for this to occur.

Emergency (Backup) Power Checks:

Check #1. Check to ensure that emergency power consists of a protected independent backup power source that provides a minimum of 8-hours operating battery and/or generator power. When batteries are used for emergency power, they shall be maintained at full charge by automatic charging circuits. The manufacturer's periodic maintenance schedule shall be followed and results documented.

Check #2. Power Source and Failure Indication: Check to ensure that an illuminated indication exists at the Power Control Unit (PCU) of the power source in use (AC or DC).

Check #3. Check to ensure equipment at the IDS/AECS monitor station indicates a failure in power source, a change in power source, and the location of the failure or change.

TACTICAL ENVIRONMENT: This check is applicable where Vaults/Secure Rooms are used to protect classified materials or systems in a tactical environment. The only exception will be for urgent (short term) tactical operations or other contingency situations where fixed facilities and equipment are not yet present or incapable of being used.

Check Content Reference

M

Target Key

2506