SV-55754r2_rule
V-43025
RTS-VTC 7200
RTS-VTC 7200
CAT II
10
Install cabling and equipment in accordance with the CNSSAM TEMPEST/01-13, RED/BLACK Installation Guidance.
Depending on the TEMPEST ZONE, the separation requirements are:
- Minimum equipment separation - 50 cm or 1m
- Minimum cable separation - 5 cm or 15 cm
Review the documentation and based on the TEMPEST ZONE in the CNSSAM TEMPEST/01-13, RED/BLACK Installation Guidance, verify whether the required separations between RED and BLACK equipment and cables have been met. This includes cable routing inside equipment cabinets. Depending on the TEMPEST ZONE, the separation requirements are:
- Minimum equipment separation - 50 cm or 1m
- Minimum cable separation - 5 cm or 15 cm
If the cables or equipment are closer than the minimum cable and equipment separation distances, this is a finding.
In the event a CTTA has reviewed the system’s installation and provided a favorable report or certification, this is not a finding.
V-43025
False
RTS-VTC 7200
Review the documentation and based on the TEMPEST ZONE in the CNSSAM TEMPEST/01-13, RED/BLACK Installation Guidance, verify whether the required separations between RED and BLACK equipment and cables have been met. This includes cable routing inside equipment cabinets. Depending on the TEMPEST ZONE, the separation requirements are:
- Minimum equipment separation - 50 cm or 1m
- Minimum cable separation - 5 cm or 15 cm
If the cables or equipment are closer than the minimum cable and equipment separation distances, this is a finding.
In the event a CTTA has reviewed the system’s installation and provided a favorable report or certification, this is not a finding.