Install cabling and equipment in accordance with CNSSAM TEMPEST/01-13, RED/BLACK Installation Guidance. Depending on the TEMPEST ZONE, the separation requirements are:
- Minimum equipment separation - 50 cm or 1m
- Minimum cable separation - 5 cm or 15 cm
Review the documentation and based on the TEMPEST ZONE in the CNSSAM TEMPEST/01-13, RED/BLACK Installation Guidance, verify whether the required separations between RED and BLACK equipment and cables are met. This includes cable routing inside equipment cabinets. Depending on the TEMPEST ZONE, the separation requirements are:
- Minimum equipment separation - 50 cm or 1m
- Minimum cable separation - 5 cm or 15 cm
If the cables or equipment are closer than the minimum cable and equipment separation distances, this is a finding.
V-43045
False
RTS-VTC 7400
Review the documentation and based on the TEMPEST ZONE in the CNSSAM TEMPEST/01-13, RED/BLACK Installation Guidance, verify whether the required separations between RED and BLACK equipment and cables are met. This includes cable routing inside equipment cabinets. Depending on the TEMPEST ZONE, the separation requirements are:
- Minimum equipment separation - 50 cm or 1m
- Minimum cable separation - 5 cm or 15 cm
If the cables or equipment are closer than the minimum cable and equipment separation distances, this is a finding.